Continue Testing of our Pressure Sensor
In our efforts to continue to test and characterize our cleanroom pressure sensor we built a miniature cleanroom out of a cardboard box and an old computer fan. To improve the ability of this home-made, leaky chamber we sealed the entire box in plastic tape and punched a very tiny hole in the top of the box. These addons certainly did not make the box clean but it did make it possible to create a small positive pressure in the box, which we dubbed “test-chamber A”. The A is for amateur- thrown-together in an hour.
When we powered the fan we were able to generate a positive pressure of between 0.023 and 0.041″ of water. Our Cleanroom pressure sensor, which we installed with a passive wall plate, was able to correctly display and log the readings over several days. It responded immediately to changes in the pressure when the fan was turned off, going to 0.000″ within about 20 seconds. Once the fan was turned by on the pressure built up to the expected 0.030″ within a minute.
One thing we noticed was that the pressure bounced back and forth a bit reflecting the changes in pressure as air escaped through not only the pin hole in the top of the box but also through the fan itself. This very much reflects what happens in a normal sized clean room. The only way to stop the fluctuation would have been to cover the fan and the pin hole once the pressure had built up. Assuming the box was completely sealed the pressure would have stabilized at some value. Actual cleanroom pressures bounce around a bit also as air escapes through door frames, around fan enclosures and other minute openings. This is normal and is reflected in the pressures displayed on the QuickCheck monitor. It is possible to buffer the pressure a bit by averaging the pressures, which is allowed by the 2di CleanRoom monitor. The average setting can be changed on the sensor setup menu to fast, medium or slow. Setting the averaging to medium or slow would cause the displayed pressure to be a little more stable. However, bear in mind that we are measuring very small pressures, down to thousands of an inch, so any small change in the environment will cause a change in pressure
Step two was to test the QuickCheck display, which we did by setting the alarm pressure to 0.010″.
. Once the fan was turned off the pressure reading turned red indicating that it had dropped below our alarm threshold. And after 10 minutes the alarm sounded, the screen flashed, and an email message was sent showing that the pressure had fallen below the safe threshold.
We did not hook the strobe up of this test but had it been in place the strobe would have begun flashing. The ten minute delay in the alarm was set in the alarm menu to eliminate false alarms which might occur if the door had been opened. (Not a likely scenario for our miniature cardboard box). This delay feature is very important for our customers who do not want to be texted every time someone opens the door causing a drop on room pressure.
Our very limited testing has verified that the 2di CleanRoom pressure sensor can pick up very small changes in pressure and responds in every way expected.